GNB Industrial Power 6-90G13 VRLA-AGM Battery 600Ah 12 Volts
Details
GNB Industrial 600Ah 12VDC VRLA Battery
The Absolyte GP battery is of the valve-regulated lead-acid (VRLA) design and so can operate with lower maintenance (e.g. no maintenance water additions) in comparison to conventional flooded lead-acid batteries. The Absolyte GP VRLA design is also inherently safer than conventional flooded lead-acid batteries. Under normal operating conditions and use, the Absolyte GP battery minimizes hydrogen gas release, and virtually eliminates acid misting and acid leakage.
Features & Specifications:
- Battery Voltage: 12 Volts DC
- Total Amp-hours @ 20 hour rate: 600 Amp-hours
- Total Amp-hours @ 100 hour rate: 720 Amp-hours
- Weight: 557 pounds
- Dimensions (L x W x H): 35.19" x 23.56" x 8.53"
- Electrolyte – 1.310 specific gravity acid (nominal)
- Safety vent – 3-10 psi opening pressure, self-resealing
- Terminals – Solid copper insert
- Positive plate – Patented lead calcium tin silver alloy
- Negative plate – Lead calcium grid alloy
- 20 years design life in float applications at 25°C (77°F)
- 1200 cycles to 80% DOD at 25°C (77°F)
- Operating temperature – Temperature excursions between -40°C (-40°F) to +50°C (122°F) allowed (battery performance and life will be affected)
- Self-discharge – 0.5 to 1% per week maximum @ 25°C (77°F)
- Float voltage – 2.23 to 2.27 Volts per cell
Product Documents